MASK Control Systems - Bespoke Industrial Automation & Control Systems UK
Tier III / Tier IV Emergency PowerENA EREC G99 / G100 Compliant16 min read

Data Centre Emergency Power & ATS Synchronization Automation: Generator Paralleling, G99 & EPMS Systems

Mission-critical emergency power automation engineered for UK hyperscale, colocation, and enterprise data centres. MASK designs and commissions multi-generator paralleling switchgear, closed-transition automatic transfer switches (ATS make-before-break), ENA EREC G99 grid-tie synchronization, automated block load shedding, and sub-cycle EPMS disturbance recording.

Data centre generator paralleling switchgear, Form 4 busbars and ATS control instrumentation
Critical Standby Generation Switchgear
Multi-Gen Paralleling | Closed-Transition ATS | Zero Inrush Drops
BLACK-START TIME
< 12 sec
Auto-Sync to Common Bus
ATS OVERLAP TIME
< 100 ms
Closed-Transition Soft Load
GRID COMPLIANCE
EREC G99
RoCoF & Vector Shift Protection
FAULT RATING
65kA to 100kA
BS EN 61439 Form 4 Type 7
STANDARDS & FRAMEWORKS:
ENA EREC G99 & G100 (UK Grid Code)BS EN 61439-2 (Form 4 Type 6/7 Switchgear)Uptime Institute Tier III / IV Concurrent MaintainabilityBS 7671 18th Edition (IET Wiring Regulations)ISO 8528-5 (AC Generating Sets)Woodward Easygen / ComAp / Deif Controllers
Power Continuity Challenges

Grid Vulnerability, Block Load Stalls & Transfer Transient Risks

When a utility grid outage strikes a 20 MW to 100 MW data centre campus, the electrical switchgear must react instantly. Standby generator sets must start, synchronize to the common bus, and take over the building load within seconds without frequency dips, reverse power trips, or out-of-phase breaker closures. A split-second failure during transfer compromises downstream UPS batteries, trips chiller plant compressors, and exposes IT workloads to catastrophic dropouts.

Block Load Frequency Stalls

Stepping full chiller and UPS rectifier loads onto cold engines in a single step causes severe turbocharger lag and engine speed drops below 47.5 Hz. Under-frequency relays trip the generator offline, causing cascading power failure across the entire critical bus.

Open-Transition Voltage Sags & Inrush

Conventional break-before-make ATS switches disconnect inductive loads for hundreds of milliseconds. When power is reconnected, out-of-phase residual magnetic fields generate destructive inrush currents up to 20x nominal, tripping upstream breakers and degrading transformers.

Degraded Diesel Fuel & Day Tank Failures

Generators sitting idle for months accumulate microbial growth, water condensation, and asphaltene sludge in bulk fuel tanks. When an extended outage demands 24-hour continuous running, fuel injectors foul or transfer pumps fail, stalling generators under peak IT load.

Basic Standalone Packaged Generator Controls vs MASK Engineered Paralleling Architecture

How our integrated industrial switchgear automation delivers Tier III / IV concurrent maintainability.

System CharacteristicBasic OEM Packaged Generator PanelMASK Engineered Paralleling Switchgear Architecture
Paralleling & SynchronizationSingle generator per ATS. No bus paralleling or N+1 capacity sharing.Multi-generator digital load controllers (Woodward/ComAp/Deif) with active kW/kVAR sharing.
Transfer Mode to GridOpen-transition (break-before-make). Power interruption cycles UPS batteries during tests.Closed-transition (make-before-break, <100ms overlap). Seamless monthly testing with zero disruption.
Dead-Bus Closing InterlockHardwired timer relays prone to welded contacts and out-of-phase bus closing.Deterministic first-up digital arbitration logic with hardware and software synch-check cross-checks.
Load Shedding / Step LoadingAll loads connected at once. High risk of generator stall during cold block loads.Programmable multi-stage priority shedding via redundant PLCs; mechanical loads staged safely.
UK Grid ComplianceBasic over-current relays. Non-compliant with DNO parallel operation rules.Full ENA EREC G99 / G100 certified loss-of-mains (RoCoF df/dt, vector shift) and export limiting.
Power Quality & DiagnosticsBasic analog volt/frequency gauges. No historical fault waveform capture.EPMS SCADA with 1024 samples/cycle transient waveform capture, trip coil health, and SOE logs.
Core Engineering Capabilities

Five Technical Pillars of Data Centre Standby Power Automation

From high-speed generator paralleling switchgear to closed-transition transfer schemes and G99 grid interconnects, our engineering ensures fault-tolerant operation under extreme utility grid contingencies:

01

Multi-Generator Paralleling Switchgear & Isochronous Load Sharing

Paralleling multiple 2 MVA to 3.5 MVA generator sets requires sub-cycle synchronization and active load balancing. MASK integrates multi-unit digital paralleling controllers (Woodward Easygen, ComAp InteliGen, or Deif AGC-4) coordinated with fail-safe PLC switchgear. Generators execute deterministic dead-bus arbitration, synchronizing and sharing real (kW) and reactive (kVAR) load isochronously without hunting or circulating currents.

Deterministic Dead-Bus First-Up Arbitration Logic
Active Isochronous kW and kVAR Load Sharing Lines
Form 4 Type 6/7 Busbar Segregation (65kA to 100kA 1-sec)
Multi-Engine Black Start Synchronization Under 12 Seconds
PARALLELING STATS
Total Sync Window< 12 Seconds Cold
kW Load Sharing±2% Balance Accuracy
Bus Short CircuitUp to 100kA Icw
Redundancy SchemeN+1 / 2N Paralleled
02

Closed-Transition Automatic Transfer Switches (Make-Before-Break)

Executing monthly emergency generator runs on open-transition switches forces the entire data centre onto battery power twice per test, increasing battery degradation and risking dropped loads. MASK engineers closed-transition ATS controls that synchronize generator output with the live utility supply. Sources overlap for under 100 milliseconds with soft power ramping, ensuring transparent load transfer with zero electrical disturbance.

Make-Before-Break Closed Transition (<100 ms Overlap)
Synchronizing Check Relays (Voltage, Frequency, Phase Angle)
Dual Mechanical and Electrical Interlocking to BS 7671
Zero Battery Cycling During Routine Maintenance Testing
TRANSFER PERFORMANCE
Overlap Duration< 100 ms Maximum
Voltage Sag0% Transient Sag
Phase Window±5° Synch Acceptance
Fail-Safe FallbackIn-Phase Open Transition
03

ENA EREC G99 / G100 Mains Protection & Grid Interconnection Automation

Operating standby generation in parallel with the UK electrical network (for test runs, peak lopping, or Demand Side Response) mandates full compliance with Energy Networks Association (ENA) EREC G99 and G100 regulations. MASK engineers G99 protection cubicles equipped with multi-function loss-of-mains (RoCoF df/dt and vector shift) relays, reverse power monitoring, and DNO-witnessed commissioning documentation.

ENA EREC G99 Type Tested Protection Panels
RoCoF (df/dt) & Vector Shift Loss of Mains Protection
G100 Export Limitation Schemes with Hardwired Intertrips
DNO Witness Testing Support (UKPN, National Grid, SSEN)
GRID COMPLIANCE
UK StandardENA EREC G99 / G100
RoCoF Threshold1.0 Hz/s with 500ms Delay
Export LimitingG100 Certified Multi-Stage
Relay ManufacturersComAp, Woodward, SEL
04

Priority Load Shedding, Block Loading & Tie-Breaker Sequencing

Cold generator engines cannot accept 100% building load in a single step without severe frequency instability. MASK programs intelligent load-shedding and step-loading routines inside redundant PLCs. Non-critical mechanical infrastructure (chiller plants, office HVAC, battery chargers) is shed automatically, allowing essential UPS rectifiers to stabilize on generator power before mechanical stages are sequentially restored.

Multi-Stage Priority Block Loading Sequencing Logic
Automatic Under-Frequency Load Shedding (UFLS)
Air Circuit Breaker (ACB) Bus-Tie Interlock Coordination
UPS Maintenance Bypass Trapped-Key Interlock Schemes
LOAD MANAGEMENT
Initial Block LoadUp to 60% Rating
Shedding Response< 30 ms High Speed
Step TimersConfigurable 5s to 30s
Tie-Breaker TripZone Selective Interlocked
05

EPMS SCADA Integration, Waveform Disturbance & Fuel Polishing

Electrical Power Management Systems (EPMS) provide real-time visibility into switchgear status and power quality. MASK deploys high-speed power quality meters capturing voltage transients up to 1024 samples per cycle, logging breaker operating times, trip coil continuity, and harmonic distortion. Concurrently, automated fuel management panels control day-tank polishing skids and transfer pumps, preventing injector fouling.

1024 Samples/Cycle Sub-Cycle Waveform Disturbance Capture
Automated 2-Micron Diesel Fuel Polishing & Water Separation
Breaker Contact Wear & Trip Coil Health Telemetry
Redundant Modbus TCP, IEC 61850 & BACnet IP Gateways
EPMS & FUEL STATS
Waveform Resolution1024 Samples / Cycle
Fuel Filtration2-Micron + Coalescing
SOE Time-Stamping< 1 Millisecond GPS Sync
Network ProtocolsIEC 61850 / Modbus TCP
Power Topology Comparison

Isolated Standby vs Paralleled Multi-Gen vs Grid-Interactive DSR

Depending on mission criticality, facility megawatt scale, and utility grid constraints, data centres implement distinct standby architectures. Here is how MASK engineers automation across all three configurations:

Specification ParameterIsolated Standby GenerationParalleled Multi-Gen SwitchgearGrid-Interactive DSR / Peak Lopping
Start & Synchronization Time10 to 15 seconds to single load bus10 to 12 seconds; all sets paralleled to common busScheduled ramp-up; 30 to 60 seconds soft synch to live grid
Mains Transition ModeOpen-transition (break-before-make); 50-500 ms outageClosed-transition (make-before-break); <100 ms zero-dropout overlapContinuous parallel operation; base-load export or zero-export limit
Grid Compliance StandardBasic connection agreement; no parallel feedENA EREC G99 (Short-Term Parallel for Testing)Full ENA EREC G99 / G100 Export Limitation Scheme with DNO witnessed tests
Load Shedding CapabilitySingle-stage emergency trip via shunt trip breakerMulti-stage block loading and dynamic under-frequency priority shedAutomated capacity market dispatch with target import/export kW regulation
Typical MASK PlatformComAp InteliLite + Schneider Compact NSX circuit breakersWoodward Easygen 3500XT + Rockwell GuardLogix PLC + Masterpact MTZ ACBsDeif AGC-4 / Woodward + Siemens S7-1500R Redundant PLC + SEL-751 relays
Tier 1 Critical Hardware

Engineered with Industry-Standard Emergency Power Platforms

We engineer control systems complying with BS EN 61439 Form 4 Type 6/7, deployed on the hardware platforms specified by leading hyperscale and colocation operators:

PARALLELING CONTROLLERS

Woodward & ComAp Gen Controls

Woodward Easygen 3500XT and ComAp InteliGen controllers with isochronous kW/kVAR load sharing lines, dead-bus arbitration, and G99 loss-of-mains protection.

Explore Control Panel Design
REDUNDANT SWITCHGEAR PLC

Rockwell ControlLogix Redundancy

ControlLogix 5580 redundant processor pairs with Device Level Ring (DLR) I/O, automated load shedding logic, and Masterpact MTZ air circuit breaker coordination.

Explore Allen-Bradley Services
HIGH-AVAILABILITY & G99

Siemens S7-1500R & SIPROTEC

SIMATIC S7-1500R redundant controllers integrated with SIPROTEC 5 protection relays via IEC 61850 for ultra-fast busbar differential and reverse power tripping.

Explore Siemens Services
Turnkey Project Delivery

Our 5-Stage Emergency Power Commissioning Methodology

Commissioning emergency power systems for mission-critical facilities requires rigorous stage-gate progression:

01

Protection Coordination Study

Short-circuit calculations, grading curves, breaker trip settings to BS EN 61439, and ENA EREC G99 loss-of-mains study.

02

Form 4 Switchboard Build

Bespoke Form 4 Type 6/7 segregated enclosures, copper busbars up to 100kA, and in-house FAT staging with simulated load controllers.

03

Cold Wiring & Point-to-Point

On-site secondary injection testing, CT/VT polarity checks, breaker auxiliary contact wiring, and fiber network ring continuity.

04

Load Bank Step Testing

Resistive/reactive load bank testing from 25% to 110% load, turbo transient response checks, and automated block loading tuning.

05

Black Building Test & Handover

Full utility power cut simulation, closed-transition ATS return, DNO G99 witness testing sign-off, and final O&M manuals handover.

Engineering FAQ

Emergency Power Automation Questions Answered

Technical guidance on closed-transition ATS, multi-generator paralleling, and ENA G99 grid compliance.

How does closed-transition ATS transfer differ from standard open-transition transfer?
An open-transition transfer operates as break-before-make, momentarily disconnecting the load for 50 to 500 ms while switching between mains and standby generators. Closed-transition transfer operates as make-before-break, synchronizing the generator voltage, frequency, and phase angle with the grid before overlapping both sources for less than 100 ms. This achieves seamless, zero-disturbance load transfer during monthly routine generator testing without cycling UPS batteries or causing transformer inrush.
How do your control systems prevent generator tripping during sudden block loading?
When large data centre electrical loads are stepped onto standby generators, large transient inrushes can cause severe frequency dips below 47.5 Hz, risking generator under-frequency trips. MASK implements multi-stage block loading and priority load shedding in redundant PLCs. Non-critical mechanical infrastructure (chillers, air handlers, fuel polishers) is held off or shed dynamically, allowing critical UPS rectifiers to stabilize before secondary loads are re-introduced in timed, interlocked increments.
What protection relays and G99 grid compliance testing are required for mains paralleling in the UK?
Parallel operation with the UK District Network Operator (DNO) grid requires compliance with ENA EREC G99. We integrate type-tested loss of mains (LoM) protection relays providing Rate of Change of Frequency (RoCoF df/dt) and vector shift detection, over/under voltage, over/under frequency, and directional power flow relays. For export-limited sites, we engineer G100 certified reverse power limiter schemes with fail-safe trip interlocks.
How is dead-bus closing safely coordinated between multiple paralleled generators?
When utility power drops out completely and the common switchgear bus is de-energized (dead bus), multiple generator sets start simultaneously. Our paralleling controllers execute deterministic first-up arbitration: the first generator to reach nominal voltage and frequency is granted a dead-bus close command. The remaining generators synchronize automatically to the live bus before closing their respective air circuit breakers (ACBs), preventing catastrophic out-of-phase cross-closure.
What diagnostic parameters does the EPMS SCADA track on medium- and low-voltage air circuit breakers (ACBs)?
Our Electrical Power Management System (EPMS) interfaces directly with intelligent trip units (Micrologic, Ekip, STR) and protection relays. It continuously logs contact wear percentages, operating cycle counts, charging spring status, trip coil circuit continuity, phase current harmonics up to the 63rd order, and microsecond-level time-stamped sequence of events (SOE) to diagnose trip root causes immediately.
Can MASK automate fuel polishing and day-tank replenishment skids?
Yes. Stored diesel fuel degrades over time due to moisture condensation and bacterial sludge, endangering generator injectors during prolonged power outages. MASK engineers automated fuel management panels featuring duty/standby filtration pumps, 2-micron particulate filters, water coalescers, ultrasonic level sensors, magnetic float overfill cut-offs, and double-walled pipe leak detection.
Speak Directly With Mike

Protect Critical Uptime with Turnkey Standby Power Switchgear Automation

Whether designing a new hyperscale generator paralleling scheme, upgrading legacy open-transition ATS panels to closed-transition soft loading, or achieving ENA EREC G99 grid compliance, MASK delivers mission-critical electrical engineering backed by over 20 years of UK control systems experience.

Direct engineering consultation
Closed-transition make-before-break
Full DNO G99 witness testing sign-off
WhatsApp